How to read a single line diagram
A plain guide to the drawing every switchboard starts from, and what to look for before you sign it off.
blog-sld.jpg Every switchboard we build starts from one drawing: the single line diagram, often called the SLD. It is the map of the board. If you can read it, you can check that what arrives on site is what you asked for. This guide walks through the parts of a typical diagram and the questions worth asking before you approve one.
Why it is called single line
A low voltage supply in South Africa is normally three phase, with a neutral and an earth. Drawing every conductor would turn the page into a tangle. A single line diagram draws the whole circuit as one line and lets symbols and notes carry the detail. One line from the supply to the main switch means three phases and a neutral, unless the drawing says otherwise.
Start at the top
Most diagrams read from top to bottom, in the same direction the power flows. At the top you will find the incoming supply. Look for:
- Where the power comes from. A utility transformer, a mini substation, a generator, or more than one of these.
- The supply rating. Usually a current in amps, sometimes with the transformer size in kVA.
- The fault level. The current that could flow during a short circuit, written in kA. Every device below it must be able to withstand and interrupt that current safely. If the fault level is missing, ask for it.
The main switch
Directly below the supply sits the incomer: the main breaker or switch that can isolate the whole board. The symbol and the note beside it tell you the type of device, its current rating and its breaking capacity. Check that the breaking capacity is at least the fault level written above it.
If the board has a generator or a second supply, you will see a changeover arrangement here. It might be two breakers with an interlock drawn between them, or a single changeover switch. The point is that the two supplies can never be connected together. If the diagram does not make that clear, ask how the interlock works.
The busbar
Below the incomer you will see a thick horizontal line. That is the busbar, the copper that carries power across the board to every outgoing circuit. Its rating should be written beside it. It should be at least as large as the incomer.
Some boards split the busbar into sections, for example normal and essential supply in a hospital or office. A bus section switch or a gap in the line shows where one section ends and the next begins.
Metering
Meters and current transformers usually appear just after the incomer, or on individual feeders. A current transformer is drawn as a small circle or loop around the line, with its ratio written beside it, for example 800/5. Check that what is metered matches what you need to know: the whole building, each tenant, or each large load.
The outgoing feeders
Hanging down from the busbar are the outgoing circuits. Each one should show:
- the protective device and its rating
- what it feeds, for example "DB Ground floor" or "Chiller 2"
- the cable size, if the designer has included it
This is where most mistakes are caught. Read each feeder and ask whether the name matches the building, whether the rating matches the load schedule, and whether any circuit is missing.
Spare ways
Good diagrams show spare and space ways: spare means a device is fitted but not connected, space means room is left for one later. Buildings change. A board with no room to grow is expensive to extend. If the diagram shows none, it is worth asking why.
Earthing and protection
Look for the earth bar, the neutral arrangement and any earth leakage or surge protection. These are often drawn as notes rather than symbols, so read the small print in the corners of the sheet too.
The title block
Finally, read the title block. It tells you the project, the revision letter and the date. Make sure the drawing you approve is the latest revision, and that everyone on the project is working from the same one.
Before you sign it off
A quick checklist:
- Is the supply rating and fault level shown?
- Does every device have a breaking capacity at or above the fault level?
- Does the busbar rating match or exceed the incomer?
- Does every feeder match a real load, with the right name?
- Are spare and space ways included?
- Is it the latest revision?
If you can answer yes to all six, you are in a good position to approve the drawing. If you are not sure about any of them, send it to us with your questions. A short conversation at drawing stage saves a great deal of time once the board is built.